T rear with double protection surge arrestor (6~35kV)

Applications:

Provide lightning protection and over-voltage protection, can effectively ensure the safe operation of the power grid.


Features:

Surge arrester with a unique escape from the explosion-proof device (ejector arrester valve).

Can effectively prevent arrester valves from aging off moment, the ground to form a high voltage and external shield to form a pathway discharge.


Technical properties

Item

AHY5WZ-10/27

AHY5WS-10/30

AHY5WS-13/36

AHY5WZ-17/45

AHY5WS-17/50

System Nominal

Voltage(kV)

6

6

10

15

15

Rated Voltage

10

10

13

17

17

Continuous Operation

Voltage (kV)

8.0

8.0

10.4

13.6

13.6

Nominal Discharge

Current(kA)

5

5

5

5

5

Steep Current Impulse

Residual Voltage (kV)

≤31.0

≤34.6

≤41.3

≤51.8

≤57.5

Lightning Impulse

Residual Voltage(kV)

≤27.0

≤30.0

≤36.0

≤45.0

≤50.0

Switching Impulse

Residual Voltage(kV)

≤23.0

≤25.6

≤30.7

≤35

≤42.5

Long Duration Current

Impulse withstand(A)

150

75

150

150

100

High Current Impulse

Withstand (kA)

65

65

65

65

65


Item

AHY5WZ-26/66

AHY5WZ-32/85

AHY5WZ-34/90

AHY5WS-34/85

System Nominal

Voltage(kV)

20

20

20

20

Rated Voltage

26

32

34

34

Continuous Operation

Voltage (kV)

20.8

25.6

27.2

27.2

Nominal Discharge

Current(kA)

5

5

5

5

Steep Current Impulse

Residual Voltage (kV)

≤76

≤95

≤104

≤95

Lightning Impulse

Residual Voltage(kV)

≤66

≤30.0

≤90

≤85

Switching Impulse

Residual Voltage(kV)

≤56

≤75

≤80

≤75

Long Duration Current

Impulse withstand(A)

150

150

150

200

High Current Impulse

Withstand (kA)

65

65

65

65


Item

AHY5WZ-51/134/400

AHY5WS-51/134/600

AHY5WZ-51/134/800

System Nominal

Voltage(kV)

35

35

35

Rated Voltage

51

51

51

Continuous Operation

Voltage (kV)

40.8

40.8

40.8

Nominal Discharge

Current(kA)

5

5

5

Steep Current Impulse

Residual Voltage (kV)

≤154

≤154

≤154

Lightning Impulse

Residual Voltage(kV)

≤134

≤134

≤134

Switching Impulse

Residual Voltage(kV)

≤114

≤114

≤114

Long Duration Current

Impulse withstand(A)

400

600

800

High Current Impulse

Withstand (kA)

100

100

100



Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Related products
underground cable termination
Heat Shrinkable Cable Straight Termination Kit Cable Joint(8.7/15kV-26/35kV)

Straight Through Jointing Kit offered provide for suitable insulating and sealing performance and feature use of heat shrinkable and resin.

Elbow Surge Arrester
Elbow Surge Arrester (6~15kV)

Applications:

suitable for American 200A electrical system, installed on the 200A interface of the high voltage outlet of American box substation, ring main cabinet, cable branch box, buried transformer and other electrical equipment to provide overvoltage protection for electrical equipment.

The product interface complies with the 200A casing design in the standard IEEE386.


Cast Resin
Low Voltage Cast Resin Straight Through Joint

COTRAN cast resin joint kits are reliable jointing solutions for intermediate connectors of wires and cables. The cast resins without filler are high quality, and fast setting resin for tough ambient conditions. Ideal for power cable accessories as insulation or as protective layer in case of MV joints. The products have the advantages of excellent waterproof performance, convenient installation, excellent electrical performance and long-term immersion in water.

Insulation Piercing Connector
COTRAN Insulation Piercing Connector (JJC series)
Product Applications COTRAN JJC series insulation piercing connectors are applicable for all types of LV-ABC conductors as well as connections in service line system, building electrical system and street lighting system. installation of JJC can be easily done by tightening bolts to forceteeth penetrate insulation of main line and tap line simultaneously. Stripping of insulation is avoided for both lines. Feature Material: insulation material made of weather resistant polymer. Contact teeth made of tinned brass or copper or aluminum. Meet standard requirements: EN 50483-4, NF C33-020, NF C33-004 Specification Type Main line section (mm²) Branch section (mm²) rated current (A) Dimensions  (mm) Weight (g) Piercing Depth (mm) No. of bolts JJC888 0.75-6 0.75-6 41 21*27*23 10 1-1.5 1 JJC-1 1.5-25 1.5-10 55 27*41*62 55 1.5-2 1 JJC-2 16-95 1.5-10 55 27*41*62 55 1-2 1 JJC-3(A) 6-50 4-25 157 42*45*62 110 2.5-3.5 1 JJC-3 16-95 4-35(50) 157 46*52*87 160 2.5-3.5 1 JJC-4 50-150 6-35(50) 157 46*52*87 162 2.5-3.5 1 JJC-5 25-95 25-95 214 50*61*100 198 3-4 1 JJC-5-1 16-120 16-120 214 50*61*100 198 3-4 1 JJC-6 (35)50-150 (35)50-150 316 50*61*100 280 3-4 1 JJC-7 120-240 25-120 276 52*68*100 360 3-4 1 JJC-7-1 150-240 10-25 102 52*68*100 336 3-4 1 JJC-8 95-400 35-300 425 83*130*130 1050 5-6 2
Brazed Water Cooled Plate
New Energy Automobile Brazed Water Cooled Plate

◆High production efficiency

◆Large thermal contact area

◆Uniform and stable welding

◆Rapid thermal cooling speed

◆Thin thickness to save space

◆Easy processing and shaping

◆Good thermal exchange effect

◆Low leak risk and high reliability

Battery Pack Aluminum Cooling Plate
Energy Storage System Battery Pack Aluminum Cooling Plate

◆High production efficiency

◆Good heat exchange effect

◆Large thermal transfer area

◆High performance cost ratio

◆Rapid thermal cooling speed

◆Thin thickness to save space

◆Easy processing and shaping

◆Low leak risk and high security

Shear bolt Connector&Lug
Shear bolt Connector&Lug


The shear bolt connectors are intended for stranded and solid aluminum and copper cable, low voltage and medium voltage up to 36 kV.

They comprise cable areas 10-400 mm² even bigger for sector cable. There is also a screw sleeve for branches up to a total of 100 mm². The joint with the conductor is achieved by the screws in the connector or terminal being tightened to a predetermined torque.


Battery Liquid Cooling Sheet
New Energy Vehicle Battery Liquid Cooling Sheet

◆Large thermal transfer area

◆Flexible flow channel design

◆Rapid thermal cooling speed

◆Excellent thermalcooling effect

◆Low leakage risk and high security

◆Stable and high production efficiency

◆Good pressure resistance and strength

◆Improve battery function andperformance

Subscribe
Subscribe to our newsletter and stay up to date with the latest news and deals !

click here to leave a message

Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.

Home

Products

About

contact